Hello Everybodytoday I came with new CHALLENGE in Design of Steel Structure.Who can Solve accept this CHALLENGE ??Thanks a lot

M3H224596 -DSS -CW -2017 -18 -SemB -Part Time Batch BNE -CEN

Table 1: Relevant data to be used by each student for the design of plate girder. [Refer data shown against your student

number]

Sl. No Student Number Figures Dimensions Steel Grade (Both for Roof Slab and Floor Slab)

Concrete Grade (Both for Roof Slab and Floor Slab)

Roof Slab Floor Slab

Horizontal Direction

Vertical Direction A (m)

B (m)

Overall Depth of slab (mm)

Load due to floor finishes (kN/m 2)

Imposed Load (kN/m 2)

Overall Depth of slab (mm)

Load due to floor finishes (kN/m 2)

Imposed Load (kN/m 2)

1 07741 Fig 3(a) &Fig3(b 9 18 S355 C35/40 160 2.75 4.50 195 1.00 2.00 2 09438 Fig2(a) &Fig2(b) 12 24 S355 C30/35 165 1.75 3.50 200 1.50 2.00 3 120987 Fig1(a) &Fig1(b) 12 24 S275 C40/45 170 2.50 3.00 150 2.00 2.00 4 130365 Fig1(a) &Fig1(b) 14 28 S275 C35/40 180 1.80 4.00 150 2.50 2.50 5 130917 Fig1(a) & Fig1(b) 8 18 S275 C30 /35 18 5 1.80 2.50 195 1.00 4.50

6 131034 Fig 3(a) & Fig3(b) 10.50 21 S275 C40 45 18 0 2.50 2.50 185 1.25 3.50

7 140427 Fig2(a) & Fig2(b) 12 24 S355 C35 40 170 1.80 4.00 170 0.80 160 8 140458 Fig1(a) & Fig1(b) 10 20 S355 C35 /40 185 2.00 3.00 180 0.80 175 9 140479 Fig2(a) & Fig2(b) 14 28 S355 C40 /45 165 1.80 3.00 160 1.00 3.00 10 140529 Fig 3(a) & Fig3(b) 9 18 S355 C35 /40 160 2.25 3.50 170 1.00 3.00 11 140642 Fig1(a) & Fig1(b) 12 24 S355 C30 /35 16 5 1.80 2.50 195 1.00 4.50

12 140708 Fig2(a) & Fig2(b) 14 28 S355 C30 /35 18 0 2.50 2.50 185 1.25 3.00

13 150352 Fig 3(a) & Fig3(b) 8.75 16.50 S275 C40 /45 180 1.80 4.00 170 0.80 3.00 14 150405 Fig 3(a) &Fig3(b 7.50 15 S355 C35 /40 185 2.00 3.00 180 0.80 3.50 15 170332 Fig1(a) &Fig1(b) 8 18 S355 C35 /40 165 1.80 3.00 160 1.00 4.00 16 170348 Fig2(a) &Fig2(b) 14 28 S355 C30 /35 160 2.25 3.50 170 1.00 2.50

NOTE:

1. Refer to the attached building plan.

2. Refer Table 1. The numerical values of the data applicable to each student number is different.

Carefully use the data shown against your student number. These values will be recorded and cross

checked when the course work is submitted.

3. All designs shall be carried out by Limit State Method of design as per British Standard

Code clauses and sub -clauses. These clauses must be clearly mentioned in the design calculations.

4. Any missing data ma y be suitably assumed and must be clearly mentioned in the solutions.